Schneider Electric A9C61425

A9C61425 Reflex iC60N integrated control MCB, 25 A, 4P, curv

MPN A9C61425
Obsolete

Schneider Electric Acti9 Reflex iC60N integrated control circuit breaker, 25 A, 4P, curve B, 20 kA Icu at 240 V AC, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9C61425 specifications
ParameterValue
Trip unit typeThermal-magnetic
Main product or component typeIntegrated control circuit breaker
Coil voltage230 V AC 50/60 Hz 24 V AC 50/60 Hz 48 V AC 50/60 Hz 24 V DC 48 V DC
Insulation voltage ui500 V AC
IP ratingIP20
Pollution degree3
ColorWhite
Depth77 mm
Width117 mm
Height84 mm
Electrical life cyclesAC-1: 50000 cycles AC 50 Hz
Mechanical life cycles50000 cycles
ApplicationControl Distribution

Product details

The Schneider Electric A9C61425 is a Reflex iC60N integrated control circuit breaker from the Acti9 range — a 4-pole, 25 A, curve B unit that combines overcurrent protection with local and remote switching in a single DIN-rail package. It is rated for control-distribution applications, meaning it handles both the protective and the on/off control function for a circuit, typically in a panel feeding a motor starter, lighting contactor, or similar load that needs operator or PLC-driven switching. Rated 25 A continuous, it breaks up to 20 kA Icu at 240 V AC and 10 kA Icu at 415 V AC, per EN/IEC 60947-2, which covers most commercial and light industrial panel fault levels.

This breaker accepts multiple control signal types: a maintained low-voltage pulse, an impulse (momentary) signal, or a maintained continuous command. The control circuit voltage options cover 230 V AC, 24 V AC, 48 V AC, 24 V DC, and 48 V DC — so it can be driven directly from a 24 V DC PLC output or a 230 V AC pushbutton station without an interposing relay. The toggle ON/OFF button on the front gives local manual override. Local signalling includes a green LED for device ON, a flashing LED for tripped or overheat conditions, and a flashing LED for device ready — useful for quick panel diagnostics without a multimeter. A contact position indicator shows whether the main contacts are open or closed.

At 117 mm wide (13 pitch units), it occupies four pole spaces plus the control module width. Depth is 77 mm, height 84 mm, so it clears most standard enclosure depths. The IP20 rating means it is intended for enclosed panels only, not washdown or outdoor exposure. Earth-leakage protection is handled by a separate block (not integrated), so if RCD protection is required, a companion Vigi iC60 or similar module must be added downstream. The 500 V AC rated insulation voltage gives headroom for 400 V line-to-line systems.

MPN
A9C61425