Schneider ATV6000C538A6666ND AC Drive, 4300 kW, 5380 kVA

MPN ATV6000C538A6666ND
Active

Schneider Electric Altivar Process ATV6000 AC Drive, 4300 kW normal duty, 5380 kVA, 3-phase, 30-pulse diode rectifier, floor-standing enclosure, CULus CE UKCA.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV6000C538A6666ND specifications
ParameterValue
Input type30 pulse diode rectifier bridge
Display type10 inch LCD touch screen multi-language
Connector type2 RJ45 on the control block)Ethernet IP/Modbus TCP 1 RJ45 on the control block)Modbus serial
Current406 A heavy duty 471 A normal duty
Frequency50 Hz +/- 5 %
Phases3-phase
IP ratingIP31
Temp storage max50 °C
Temp storage min0 °C
Temp operating max60 °C
Temp operating min1.2 °C
Storage temperature32...122 °F (0...50 °C)
Pollution degreePollution degree 2
Depth66.9 in (1700.0 mm)
Width234.6 in (5960.0 mm)
Height109.9 in (2791.0 mm)
Operating temperature32...104 °F (0...40 °C) 104...122 °F (40...50 °C) with derating factor -13...158 °F (-25...70 °C) during transport

Product details

4300 kW motor drive, 5380 kVA apparent power

This is the Schneider Electric Altivar Process ATV6000C538A6666ND, a medium-voltage AC drive from the ATV6000 series. It's built for big loads: 4300 kW normal duty, 3740 kW heavy duty, with a 5380 kVA apparent power rating. The 30-pulse diode rectifier front end keeps input harmonics under 3% THDI per IEEE 519-1992, and the power factor sits at 96% — no extra filtering or PF correction gear needed for most installations.

Line current and power losses — heavy vs normal duty

Line current draw is 406 A in heavy-duty service and 471 A under normal duty — the difference reflects the headroom built into the IGBT inverter cells for overload capacity. Power losses run 141.6 kW at heavy duty and 162.8 kW at normal duty. That's the heat you need to move through the forced-convection cooling system, so the floor-standing enclosure's ventilation path matters.

Active production, quoted to order

Compliance documentation covers CULus, CE, and UKCA marking, plus standards IEC 61800-3, IEC 61800-4, IEC 61800-5-1, IEC 60529, IEEE 519:1992, EN/IEC 60076, and UL 347A.

MPN
ATV6000C538A6666ND