C25F34V100 ComPacT NSX 100A MCCB, 85kA Icu at 240V

MPN C25F34V100
Active

Schneider Electric ComPacT NSX, NSX250F, Earth leakage circuit breaker, 3P, 100 A at 40 °C, MicroLogic 4.2 trip unit, 85 kA Icu at 240 V AC.

$1,179.33 – $2,469.96 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C25F34V100 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

C25F34V100 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

It's a 3-pole, 100 A frame with a MicroLogic 4.2 electronic trip unit that combines overload (L), short-time short-circuit (So), instantaneous short-circuit (I), and earth-leakage (R) protection in one device. The 85 kA Icu at 240 V AC (36 kA at 415 V, 35 kA at 440 V) means it can safely interrupt fault currents up to those levels without upstream fuses — a key spec for high-fault panels where you want selective coordination. The integrated earth-leakage protection (R function) eliminates a separate RCCB or ground-fault relay, saving two module widths on the DIN rail.

The 105 mm width, 161 mm height, and 86 mm depth fit standard ComPacT NSX cutouts. Front connections top and bottom — no rear-access bus required, which simplifies gland-plate layout and busbar routing in a distribution panel. IP40 enclosure protection (IK07 impact) suits it for clean indoor panels.

It's specified against EN/IEC 60947-2 and UL 60947-4-1, so it carries the approvals for both IEC and North American installations. The dual-standard listing simplifies BOM management for multinational projects.

If your panel ambient runs hotter, you'll need to derate — but the MicroLogic 4.2 is electronic, so the trip curve stays accurate across temperature, unlike a thermal-magnetic breaker that drifts with ambient heat. At 415 V it's 36 kA — still substantial for most industrial distribution. The 'F' breaking capacity code (36 kA at 415 V) tells you this is the standard-interrupting version of the NSX250 frame, not the high-interrupting 'H' or 'S' variants. Electrical durability: 20,000 cycles at 440 V at half rated current, 10,000 at full rated current. That's typical for a molded-case breaker — fine for distribution switching a few times a year, but not rated for frequent motor starting duty where you'd want a contactor.

MPN