Skip to main content
Schneider Electric C25F34V250

Schneider Electric C25F34V250 ComPacT NSX MCCB, 250A, 85kA

MPN C25F34V250
Active

Schneider Electric ComPacT NSX, NSX250F, Earth leakage circuit breaker, 3P, 250A at 40°C, MicroLogic 4.2 trip unit, 85 kA Icu at 240 V AC.

$1,179.33 – $3,300.48 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C25F34V250 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C25F34V250 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The C25F34V250 carries a full breaking capacity table across common voltages, not just one headline number. At 380/415 V AC it's rated 36 kA Icu; at 480 V AC (UL) it's 35 kA Icu; at 600 V AC it drops to 15 kA Icu. The 85 kA at 240 V AC is for North American 240/120 V split-phase service. For selectivity studies, the Ics (service breaking capacity) isn't listed here — you'd need the full datasheet to confirm whether Ics equals Icu or is a percentage. The EN/IEC 60947-2 standard this breaker is certified to requires both ratings to be published; the evidence here gives Icu only, so verify Ics for your specific coordination study.

Mounts on a backplate — no DIN rail for this frame size. The 161 mm height, 105 mm width, and 86 mm depth mean it needs a cutout or mounting plate sized for a 3-pole MCCB of this class. Connection pitch is 35 mm, which is standard for busbar or cable lugs on NSX frames. Both upside and downside connections are front-facing, so busbar runs and cable exits are on the same plane — good for a tidy panel layout. The IK07 impact rating means it can survive a 2 J hammer blow — standard for switchgear.

Earth-leakage protection — built in, not added on

The earth-leakage protection is integrated into the MicroLogic 4.2 trip unit, not a separate add-on module. That means the R (residual) protection curve is part of the same electronic package that handles overload and short-circuit. The operating mode uses the IΔn rotary switch to set the leakage trip threshold — no external relay or toroid to wire. The local signalling includes a flashing green LED for ready-to-operate, a red LED at 105% Ir for overload, and an orange LED at 90% Ir as a pre-alarm — useful for troubleshooting without opening the panel door.

Overvoltage category IV means it's suitable for the point where the utility feed enters the building, not just downstream distribution. The utilisation category is A, which means it's not intended for frequent switching of motors or transformers — it's a distribution breaker, not a motor circuit protector. The electrical durability figures give you the expected number of operations under load: 20,000 cycles at 440 V at half rated current, 10,000 at full rated current. These matter for maintenance planning on a panel that sees frequent switching.

MPN
C25F34V250