Schneider Electric C40F34V400

Schneider Electric C40F34V400 ComPacT NSX400F MCCB, 400 A, 4

MPN C40F34V400
Active

Schneider Electric ComPacT NSX series, C40F34V400, 3P earth leakage MCCB, 400 A at 40 °C, 36 kA Icu at 415 V AC, MicroLogic 4.3 electronic trip unit, integrated earth-leakage protection.

$1,782.43 – $4,278.96 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C40F34V400 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 20 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
IP ratingIP40
Terminal pitch45 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C40F34V400 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth110 mm
Width140 mm
Height255 mm
Electrical life cycles12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In
Mechanical life cycles15000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The C40F34V400 is a 3-pole ComPacT NSX400F earth-leakage circuit breaker from Schneider Electric, rated 400 A at 40 °C with a MicroLogic 4.3 electronic trip unit. The 36 kA Icu at 415 V AC (per EN/IEC 60947-2) is the breaking capacity that governs most European 400 V distribution panels — it tells you this breaker safely interrupts a fault up to 36 kA without failing, which is the figure a panel builder uses for SCCR coordination downstream. The 400 A trip rating means it protects a 400 A feeder or a large motor control center bus; the electronic trip unit gives adjustable long-time (L), short-time (So), instantaneous (I), and earth-leakage (R) protection curves, so you set the trip thresholds to the load, not the other way around. Integrated earth-leakage protection (R function) is built into the trip unit — no external RCD module needed. The 20-minute thermal memory before and after tripping means the breaker remembers the thermal state of the conductors even after a short interruption, preventing nuisance re-closure on a still-hot circuit. Mounting is backplate, horizontal or vertical, with front connections top and bottom; the 140 mm width and 255 mm height fit standard ComPacT NSX cutouts.

The F breaking capacity code delivers 36 kA Icu at 415 V AC, but the same breaker is rated 40 kA at 240 V, 30 kA at 440 V, 25 kA at 500 V, 20 kA at 525 V, and 10 kA at 690 V.

Panel integration and environmental ratings

IP40 front face (finger-safe against tools >1 mm) and IK07 impact resistance per IEC 62262 — suitable for enclosed distribution boards where incidental contact is possible. The 110 mm depth fits standard NSX enclosures; backplate mounting with horizontal or vertical orientation gives flexibility in tight cabinets.

MPN
C40F34V400