Skip to main content
Schneider Electric C60H4P40AD

Schneider Electric C60H4P40AD C60 MCB, 40 A, D Curve, 4P, 10

MPN C60H4P40AD
Obsolete

Schneider Electric Multi9 C60 series, C60H4P40AD, miniature circuit breaker, 40 A, D curve, 4 poles, 10 kA Icn at 230/400 V AC.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C60H4P40AD specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage12...440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz conforming to IEC 60947-2
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C
Storage temperature-40...70 °C
Depth73 mm
Width72 mm
Height81 mm
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...60 °C

Product details

The C60H4P40AD is a 4-pole miniature circuit breaker from Schneider Electric's Multi9 C60 range, rated 40 A at 40 °C. The 10 kA Icn at 230/400 V AC per EN 60898 covers standard commercial panel fault levels; the IEC 60947-2 ratings give higher Icu values for industrial coordination — 15 kA at 400-415 V, 30 kA at 230-240 V, and up to 50 kA at 250 V DC for the 4P configuration. That DC breaking capacity makes it usable in battery or UPS circuits where the poles are series-connected. Snaps onto a 35 mm symmetrical DIN rail, 4 modules wide at 72 mm, 81 mm tall, 73 mm deep. Thermal-magnetic trip technology with separate earth-leakage block option — the MCB itself does not include integral RCD. Suitability for isolation marked per IEC 60947-2.

MPN
C60H4P40AD