Schneider Electric C60H4P63AB

Schneider Electric C60H4P63AB Miniature Circuit Breaker, 63

MPN C60H4P63AB
Obsolete

Schneider Electric Multi9 C60H series, C60H4P63AB, 4-pole miniature circuit breaker, B-curve, 63 A, thermal-magnetic, 10 kA breaking capacity, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C60H4P63AB specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage12...440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity10 kA Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 125 V DC 2P conforming to IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to IEC 60947-2 50 kA Icu at 250 V DC 4P conforming to IEC 60947-2
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C
Storage temperature-40...70 °C
Depth73 mm
Width72 mm
Height81 mm
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...60 °C

Product details

The Schneider Electric C60H4P63AB is a 4-pole miniature circuit breaker from the Multi9 C60H series, rated at 63 A with a B-curve trip characteristic (3–5 × In magnetic tripping limit). It occupies 8 × 9 mm pitches on a 35 mm symmetrical DIN rail, so it takes 72 mm of rail width in the enclosure. The B-curve magnetic trip activates between 3 and 5 times the rated current. That suits resistive and general-purpose loads with modest inrush.

Dual-certified to IEC 60947-2 and EN 60898, this breaker carries a 10 kA Icn at 230/400 V AC under EN 60898 and a range of Icu values under IEC 60947-2: 15 kA at 400–415 V AC, 30 kA at 230–240 V AC, and 25 kA at 125 V DC (2-pole series connection). The Ics service breaking capacity sits at 7.5 kA for the 230/400 V AC EN 60898 case — meaning after clearing a fault at that level the breaker remains functional, not just safe. The thermal-magnetic trip unit handles overloads thermally and short-circuits magnetically. Rated insulation voltage is 500 V AC, and the operational voltage range covers 12–440 V AC 50/60 Hz.

Integration notes

The toggle provides local ON/OFF indication, and the contact position indicator confirms isolation visually. Maximum operating altitude is 2000 m without derating.

MPN
C60H4P63AB