Skip to main content
Schneider Electric EVS12H3MW60

Schneider Electric EVS12H3MW60 EasyPact EVS Circuit Breaker,

MPN EVS12H3MW60
Active

Schneider Electric EasyPact EVS, EVS12H3MW60, 3-pole drawout circuit breaker, 1250 A rated current, 65 kA breaking capacity at 440 V AC, electronic trip unit.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EVS12H3MW60 specifications
ParameterValue
Control typeManually operated
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width441 mm
Height439 mm
ApplicationDistribution
Operating temperature-5...70 °C

Product details

The Schneider Electric EVS12H3MW60 is a 3-pole drawout circuit breaker from the EasyPact EVS range, rated 1250 A at 40 °C with an electronic EVS Trip System6.0 trip unit. It provides overload (long-time), instantaneous short-circuit, short-time short-circuit, and earth-fault protection — four protection functions in one device, which means a single breaker covers feeder and fault protection without needing separate relays. Breaking capacity is 65 kA Icu at 220...440 V AC 50/60 Hz per IEC 60947-2, and 50 kA Icu at 690 V AC. The 25 ms maximum breaking time means the arc is quenched in under three line cycles at 50 Hz.

IP40 protection — suitable for indoor switchgear where large solids are excluded but not sealed against moisture. Pollution degree 4 per IEC 60664-1, meaning it's rated for continuous conductive contamination (dust, condensation), typical in industrial environments without climate control.

Category B utilization (IEC 60947-2) means this breaker is designed for selective coordination — it can hold a short-time delay to let downstream breakers clear a fault first, then trip itself if the fault persists. Electrical durability is 5000 cycles at 440/690 V without maintenance; mechanical durability is 10000 cycles without maintenance, 20000 with maintenance. That's a long service life for a main breaker in a distribution board that sees infrequent switching. That's a detail that matters for motor feeders or welder circuits with repetitive overload cycles.

MPN