Skip to main content
Schneider Electric EZC100H2050

Schneider Electric EZC100H2050 EasyPact EZC100H Circuit Brea

MPN EZC100H2050
Obsolete

Schneider Electric EasyPact EZC100H, EZC100H2050, thermal-magnetic circuit breaker, 50 A, 2 poles, 10–100 kA breaking capacity, IP20, IK07.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EZC100H2050 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeCircuit breaker
Voltage550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Insulation voltage ui690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP20
Terminal pitch25 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

EZC100H2050 additional specifications
ParameterValue
Temp storage min-35 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-35...85 °C
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Depth60 mm
Width50 mm
Height130 mm
Mechanical life cycles13000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The EZC100H2050 is a 2-pole thermal-magnetic circuit breaker from the Schneider Electric EasyPact EZC100H series, rated 50 A at 40 °C. The TM-D trip unit provides short-circuit and overload protection. The H breaking capacity code means it delivers 10 kA Icu at 550 V AC, 30 kA at 400–415 V AC, and 50 kA at 220–240 V AC — so it can interrupt fault currents up to those levels without upstream coordination issues. For DC circuits, it breaks 10 kA at 125 V DC (1P) or 250 V DC (2P). The 690 V AC rated insulation voltage and Category A utilization confirm it is designed for distribution panelboard duty, not motor-starting cycles. IP20 finger-safe terminals and IK07 impact resistance suit it for backplate mounting in a locked panel.

Deployment context

Mounts fixed to a backplate with front-front connections at a 25 mm pitch. The toggle control provides positive contact indication — the handle position shows whether the contacts are open or closed, which aids troubleshooting during commissioning.

Designed to EN/IEC 60947-1 and EN/IEC 60947-2, plus JIS C8201-2-2 and GB/T 14048.2. No earth-leakage protection is integrated; the neutral pole is unprotected. The 13,000-cycle mechanical durability is typical for distribution breakers — not a high-cycle motor-switching device.

MPN