Skip to main content
Schneider Electric EZC400N4400N

Schneider Electric EZC400N4400N EasyPact EZC400N, 400 A, 36

MPN EZC400N4400N
Active

Schneider Electric EasyPact EZC400N, circuit breaker, 400 A thermal-magnetic TM-D trip, 4-pole, 36 kA Icu at 440 V AC, IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EZC400N4400N key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui690 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP20
Terminal pitch45 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-35 °C
Temp operating max70 °C

All specifications

EZC400N4400N additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-35...85 °C
Pollution degree3 conforming to IEC 60947
ColorBlack
Depth140 mm
Width140 mm
Height255 mm
Electrical life cyclesCategory A: 4000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical life cycles10000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The headline breaking capacity is 36 kA Icu at 440 V AC 50/60 Hz per IEC 60947-2, with a higher 40 kA Icu available at 220/230 V AC. The TM-D trip gives you fixed thermal (overload) and magnetic (short-circuit) protection curves; magnetic pickup is set at 4000 A, so it clears hard faults fast while riding through motor inrush.

Standards and approvals — what they certify

This breaker carries compliance with EN/IEC 60947-2 (the main standard for low-voltage switchgear and controlgear), plus GB/T 14048.2 (Chinese national standard) and JIS C8201-2-2 (Japanese industrial standard). That triple certification covers most global project specs without a separate variant. It is also certified for isolation per IEC 60947-2 — meaning you can safely use it as a visible-break disconnect for lockout-tagout, provided the positive contact indication on the toggle matches the actual contact state. Pollution degree 3 (conforming to IEC 60947) means it's rated for the conductive dust and humidity typical in industrial enclosures, not just clean control rooms.

Fixed-mount via backplate with front-front connections — both line and load terminate on the front face, which simplifies busbar routing in a distribution panel but means you need clearance for cable bending radius on both sides. The 45 mm pole pitch matches standard Schneider EasyPact busbar systems. IP20 finger-safe protection on the front; IK07 impact rating means it survives a 2 J hammer blow (typical for panel-door mounting).

MPN