Skip to main content
Schneider Electric LC1G1504LSEA

Schneider LC1G1504LSEA Contactor, 150A AC-3, 200-500V

MPN LC1G1504LSEA
Active

Schneider Electric TeSys Giga LC1G1504LSEA 4-pole contactor, 150 A AC-3, coil 200-500 V AC/DC, mechanically durable 8 Mcycles.

$1,353.10 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LC1G1504LSEA key specifications
ParameterValue
Main product or component typeContactor
Voltage<= 460 V DC
Coil voltage200...500 V AC 50/60 Hz 200...500 V DC
Insulation voltage ui1000 V
Current150 A (at 275 A (at <40 °C) at <= 1000 V AC-1
Breaking capacity1280 A at 440 V
Utilization categoryAC-3 AC-3e AC-1 AC-5 a AC-5b AC-6 a AC-6b DC-1 DC-3 DC-5
Terminal pitch35 mm
Temp storage max80 °C
Temp storage min-60 °C
Temp operating max60 °C
Temp operating min-25 °C

All specifications

LC1G1504LSEA additional specifications
ParameterValue
Storage temperature-60...80 °C
ColorDark grey
Depth193 mm
Width143 mm
Height255 mm
Mechanical life cycles8 Mcycles
ApplicationPower switching
Operating time40...70 ms closing 15...50 ms opening
Operating temperature-25...60 °C
Permissible ambient air temperature around the device-40...70 °C at Uc

Product details

Integration brief – LC1G1504LSEA

4-pole TeSys Giga contactor in the LC1G family, set up for power switching of motor loads up to 150 A in AC-3 duty. Built-in bidirectional peak limiting on the coil suppresses switching transients – no external surge suppressor needed on the control circuit. Rated breaking capacity 1280 A at 440 V and making capacity 1890 A – numbers that confirm the contactor can handle inrush and fault clearing within the panel's protection coordination. Mechanical durability rated to 8 million cycles; for safety-rated applications the B10d is 400,000 cycles at nominal load per EN/ISO 13849-1.

Lifecycle & compliance status

Standards coverage includes EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, plus UL 60335 household appliance references. That's a single part that satisfies IEC, UL, and CSA panel builds without variant splits.

Mounting & wiring notes

Plate mount only – no DIN rail option. 4-hole pattern with 35 mm connection pitch on the power terminals; busbars sized for 25 x 6 mm cross-section or ring terminals up to 185 mm². Tightening torque on power connections is 18 N.m – tool selection matters for consistent clamping. IP2X with shrouds on the front face, so finger-safe termination if covers are fitted. Operating time: closing 40-70 ms, opening 15-50 ms – falls within typical contactor response for coordinated starter setups. Maximum electrical operating rate 600 cycles/h for AC-3, 300 cycles/h for AC-1.

Sourcing & order recommendation

Active, current-production part. No escalation needed for supply – confirm the BOM line and we can place an order against your RFQ. The 4-pole format with 1 NO + 1 NC auxiliary block built in covers most interlocking and feedback requirements; no auxiliary kit required for basic status. If the panel operates near 40°C ambient, note the rated current table: 150 A AC-3 at <= 440 V, but the AC-1 current is 275 A at <40°C – observe derating if the panel runs hot. The power dissipation per pole is 10 W in AC-1 at 275 A and 5 W in AC-3 at 150 A, so enclosure heat load is predictable.

MPN