Skip to main content
Schneider Electric ATH230D11N4

Schneider Electric ATH230D11N4 Altivar AC Drive, 11 kW

MPN ATH230D11N4
Active

Schneider Electric Altivar ATH200 series, ATH230D11N4 AC drive, 11 kW, 3-phase, 480 V, 36.6 A line current at 380 V, 25.6 A at 500 V, cabinet mount, SIL 3 STO, integrated EMC filter.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATH230D11N4 specifications
ParameterValue
Connector typeRJ45
Main product or component typeVariable speed drive
Current36.6 A 380 V 25.6 A 500 V
Frequency50...60 Hz - 5...5 %
Phases3-phase
IP ratingIP20
Temp storage max70 °C
Temp storage min-25 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-13...158 °F (-25...70 °C)
Pollution degree2
Depth7.8 in (198 mm)
Width7.09 in (180 mm)
Height13.0 in (330 mm)
Operating positionVertical +/- 10 degree
Operating temperature14...122 °F (-10...50 °C) without derating 122...140 °F (50...60 °C)

Product details

Safety-rated drive with SIL 3 STO

The ATH230D11N4 carries SIL 3 per IEC 61508 and PL e per ISO 13849-1 for its Safe Torque Off function — that means the drive can be wired into a safety circuit without an external contactor for the stop function, saving panel space and wiring time. The STO input is on a dedicated 24 V DC discrete input (1.5 kOhm impedance), so it's electrically isolated from the logic inputs — a detail that matters when you're separating the safety chain from the control PLC.

Fieldbus and I/O complement

Comes with a BACnet IP option card pre-installed, plus a 2-wire RS 485 port for Modbus serial or BACnet MS/TP — so it talks to both a BMS and a local PLC without extra hardware. The three analogue inputs cover voltage (0–10 V), bipolar differential (±10 V), and current (0–20 mA configurable), which covers most HVAC sensor types — duct static pressure, temperature, or CO2 — without signal conditioners. Six digital logic inputs plus a dedicated STO input; one of the logic inputs (DI5) can be programmed as a pulse input up to 30 kHz for flowmeter or encoder feedback.

Protection and environmental coverage

Built-in protection covers line phase loss, motor phase loss, overvoltage, undervoltage, overheating, motor overload (with PTC probe input), short-circuit between motor phases, and earth faults — so the drive handles most fault conditions without an external motor protection relay. Rated for pollution degree 2 and 5–95 % relative humidity without condensation, with an altitude derating starting at 1000 m (1 % per 100 m).

Approvals include cULus, CE, UKCA, KC, EAC, ATEX, and RCM — covers North America, Europe, Korea, Eurasia, and Australia for machine builders shipping globally.

MPN