Skip to main content
Schneider Electric ATV1200A82506666

Schneider ATV1200A82506666 AC Drive, 6897 kW, 8250 kVA

MPN ATV1200A82506666
Active

Schneider Electric Altivar 1200 ATV1200A82506666 medium-voltage AC drive, 6897 kW motor power, 8250 kVA apparent power, 36-pulse diode rectifier, 2970…3630 V supply, floor-standing enclosure.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV1200A82506666 specifications
ParameterValue
Input type36 pulse diode rectifier bridge
Protection typeGround fault protection: drive
Coil voltage220 V
Current720 A
IP ratingIP41 / IP31 / IP42
Temp storage max60 °C
Temp storage min-10 °C
Temp operating max50 °C
Temp operating min0 °C
Storage temperature-10...60 °C
Pollution degreePollution degree 2
Depth1700 mm (standard efficiency)
Width9770 mm (standard efficiency)
Height3040 mm standard efficiency
Operating positionVertical +/- 10 degree
Operating temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)

Product details

6897 kW drive, floor-standing — what it means on the line

The ATV1200A82506666 is a medium-voltage drive from the Altivar 1200 family, rated for 6897 kW motor power and 8250 kVA apparent power. That puts it squarely in the large-motor class — think mainline conveyors, crushers, large pumps or compressors in mining, cement, or oil-and-gas installations. Supply voltage range is 2970…3630 V, fed through a 36-pulse diode rectifier bridge. The 36-pulse topology cancels the 5th, 7th, 11th, and 13th harmonics at the input, which means you can often skip a dedicated harmonic filter at the point of common coupling — that saves panel space and transformer derating.

Physical footprint and installation constraints

This is a floor-standing enclosure, not a wall-mount. Dimensions are 3040 mm high, 9770 mm wide, and 1700 mm deep — so you need a dedicated drive room with a reinforced floor and a crane or forklift path for positioning. The enclosure has separate air flows for power and control sections, which keeps the electronics cooler and reduces dust ingress. Cooling is forced convection pulling 100,000 m³/h of air — that's substantial. The room's HVAC and louvers need to handle that airflow without recirculating hot exhaust. Operating altitude derating starts at 1000 m: 0.6 % current reduction per 100 m above that.

Overload duty and auxiliary supply architecture

The drive supports two overload profiles. Standard overload: 1.2× In for 60 s, 1.5× In for 3 s. High overload: 1.5× In for 60 s, 1.85× In for 3 s. Pick the profile that matches your load cycle — high overload covers crusher start-ups or extruder breakaway torque without oversizing the drive frame. Control electronics need an external 220 V AC supply rated at 3 kVA. The cooling fans run on a separate 380 V AC supply (also external). There's an optional 220 V AC/DC control supply. This split architecture means the control section stays live even if the main power is off — useful for pre-charge sequencing and diagnostics before the main contactor closes.

Compliance is solid: CE marked, designed to EN/IEC 61800-3 (EMC), EN/IEC 61800-4 (adjustable speed drives), and EN/IEC 61800-5-1 (electrical safety). Pollution degree 2 per the same safety standard, overvoltage category II. The integrated EMC filter means you don't need an external input filter for most installations.

MPN
ATV1200A82506666