Skip to main content
Schneider Electric METSEEM3561A — Circuit Protection

METSEEM3561A PowerLogic EM3561A Energy Meter, 0.5S Accuracy

MPNMETSEEM3561A
Active

Schneider Electric PowerLogic EM3500 series, EM3561A energy meter, Rogowski coil input 50...5000 A, accuracy Class 0.5S, backlit LCD, RS485 BACnet MS/TP, DIN rail mount, dark grey.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

METSEEM3561A — Identification
ParameterValue
Product / component typeEnergy meter
Device short nameEM3561A
RangePowerLogic
Product rangePowerLogic EM3500
Device applicationSub billing Partial meter
METSEEM3561A — Electrical
ParameterValue
Rated operational voltage (Ue)90...347 V AC 50/60 Hz between phase and neutral UL 156...600 V AC 50/60 Hz between phases UL 90...300 V AC 50/60 Hz between phase and neutral CE 125...300 V DC
Pole configuration3P + N
Power consumption (VA)5 VA 347 V AC between phase and neutral) 5 VA 600 V AC between phases)
METSEEM3561A — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeBy screws Clip-on
Width4.2 in (107 mm)
Height3.6 in (91 mm)
Depth2.3 in (59 mm)
9 mm pitches12
METSEEM3561A — Environmental
ParameterValue
Operating ambient temperature-22...158 °F (-30...70 °C)
Storage ambient temperature-40...185 °F (-40...85 °C)
METSEEM3561A — Approvals
ParameterValue
StandardsCSA C22.2 No 14-05 IEC 61010-1 UL 508

Product details

The METSEEM3561A is a PowerLogic EM3561A energy meter from the EM3500 series, designed for sub-billing and partial metering in 3P+N networks at 50/60 Hz. It accepts Rogowski coil input from 50 to 5000 A and delivers Class 0.5S accuracy on power and energy per IEC 62053-22 and ANSI C12.20. The backlit LCD shows per-phase voltage, current, power, power factor, and cumulative energy logs. Communication is via RS485 with BACnet MS/TP at 9600 to 115200 baud, auto-detected.

The 50...5000 A Rogowski coil input means this meter works with split-core or flexible CTs — no need to break the primary conductor for installation. The 0.5S accuracy class (IEC 62053-22 / ANSI C12.20) is the standard for revenue-grade sub-metering; it's what a utility or tenant billing application expects. The 90...347 V rated voltage covers 120/208 V, 277/480 V, and 347/600 V wye services without a PT, as long as the line-to-neutral voltage stays under 347 V. The RS485 BACnet MS/TP port lets the meter talk directly to a building management system or PLC without a gateway.

Mounts on DIN rail or by screws using the clip-on tabs. The 107 mm width (4.2 in) and 59 mm depth (2.3 in) fit a standard 4-module DIN-rail slot. The screw-terminal RS485 block is on the underside; wire it before snapping the meter onto the rail. The backlit LCD and five-digit display are readable through a panel cutout if you flush-mount it. The dark grey housing blends with the rest of the PowerLogic lineup.

Frequently asked questions

Where can I buy METSEEM3561A and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing.

What is the closest pin-compatible alternative to METSEEM3561A in this component family?

Within the PowerLogic EM3500 series, the EM3561A is the variant with Rogowski coil input and BACnet MS/TP. Other EM3500 variants differ by input type (CT vs Rogowski) or communication protocol (Modbus vs BACnet). No pin-compatible drop-in exists across series.

What compliance documentation does this brand provide for METSEEM3561A (RoHS, REACH, UL, IEC)?

The METSEEM3561A is certified to CSA C22.2 No 14-05, IEC 61010-1, and UL 508. RoHS and REACH declarations are standard for Schneider Electric PowerLogic products.

MPN
METSEEM3561A